Technical Specifications
|
SPD type:
|
T1; T2; T3 |
|
Earthing system:
|
TN-S; TN-C-S |
|
Number of poles:
|
4 |
|
Rated operating AC voltage:
|
230 V |
|
Maximum continuous operating voltage AC:
|
275 V |
|
Maximum discharge current (8/20) :
i
|
50 kA |
|
Nominal discharge current (8/20), L/N:
i
|
- |
|
Nominal discharge current (8/20), L/PE:
i
|
25 kA |
|
Nominal discharge current (8/20), N/PE:
i
|
25 kA |
|
Total discharge current (8/20), L+N->PE:
|
200 kA |
|
Impulse discharge current (10/350), L/N:
i
|
- |
|
Impulse discharge current (10/350), L/PE:
i
|
12.5 kA |
|
Impulse discharge current (10/350), N/PE:
i
|
12.5 kA |
|
Total discharge current (10/350), L+N->PE:
|
50 kA |
|
Temporary overvoltage (5s):
|
337 V |
|
Response time, L/N :
|
- |
|
Response time, L/PE:
|
25 ns |
|
Response time, N/PE:
|
25 ns |
|
Maximal back-up fuse (gL/gG):
|
160 A |
|
Rated load current for „V“ connection:
|
- |
|
Maximal back-up fuse (gL/gG) for „V“ connection:
|
- |
|
Residual current:
|
300 μA |
|
Operating temperature:
|
-40 °C .. 70 °C |
|
Humidity:
|